Air Distribution Products OPTIMA-RES-A Residential VAV System Box Data Sheet Variable Air Volume Controllers | 1 / 22
Table of Contents Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Factory Settings. . . . . . . . . . . . . . . . . . . . . . . . . . .
Variable Air Volume Controllers Description Design OPTIMA-RES-A is a compact system of supply and extract VAV controllers intended for ventilation control of residential premises. The basic functionality is continuous supply and extract air flow volume control in master/slave operation mode. Additionally, it can be switched into override operation modes like open or close damper, or minimum or maximum air flow volume control. The system of OPTIMA-RES-A system is encased in a galvanised steel box.
2 / 24 | Variable Air Volume Controllers Controls The residential VAV system is equipped with BLC4 type compact controllers in the master/slave connection. The controllers use analog input for the setpoint signal and analog output for the feedback signal. The type of the signals is DC 0 V ... 10 V. The VAV controllers are factory calibrated as standard to the air volume indicated in the table below or, upon request, they can be adjusted to site required settings of the Vmin /Vmax range.
Variable Air Volume Controllers Master (Supply Air) VAV Controller Setup Vmin adjustable between 0 and Vnom Vmax adjustable between Vmin and Vnom. Lowest possible adjustment is 20% of Vnom. Slave (Extract Air) VAV Controller Setup Vmin adjusted to 0, shall not be changed. Vmax adjusted equal Vnom, shall not be changed. Setpoint/Feedback Signal and Air Flow Volume Calculation for VAV Controller Setpoint, UC : 0 V ... 10 V Feedback, U: 0 V ...
4 / 24 | Variable Air Volume Controllers W L1 W1 K øD L Fig. 1: Dimensions of the OPTIMA-RES-A Tab. 1: Dimensions of the OPTIMA-RES-A DN øD K W W1 H H1 L L1 (mm) m v (kg) (l) 100 98 250 495 555 200 225 1080 1170 25 147 125 123 280 550 610 235 260 1180 1270 29 202 160 157,5 320 640 700 282 306 1190 1280 35 275 Ordering Code OPTIMA-RES-A- Nominal size ø (mm) Control range setup Vmin . . .
Variable Air Volume Controllers | 5 / 24 Accessories RC-C3DOC Room Controller Art. No.: 27142 Complete pre-programmed room controller intended to control heating, cooling, CO2 and other physical parameters in a zone control system. MZ3-Touch Ventilation Control Panel Art. No.: 92690 • Positioner and controller for comfort ventilation with a touch panel. • Design according to Feller EDIZIOdue®. • Manual operation with 4 steps.
6 / 24 | Variable Air Volume Controllers EC-Basic – CO2 + Temperature Room Controller Art.No. 24808 • For simultaneous control of the room temperature and the CO2 concentration (on-board sensors) based on priority of the value with the higher control difference. • Pre-adjustable heating or cooling control loop. • One DC 0 V ... 10 V VAV control output. CO2RT CO2 Room Transmitter Art. No.: 13704, 14357 Room sensor for measuring carbon dioxide concentration in indoor environments.
Variable Air Volume Controllers | 7 / 24 Technical Parameters Discharged Sound Power Level Legend ps Pa Pressure drop qV m3/h l/s Air flow volume LWA dB(A) A-weighted total discharged sound power level LW dB Non-weighted total discharged sound power level OPTIMA-RES-A-100 Air Flow ps LWA LW Non-Weighted Sound Power Level m /h Pa dB dB(A) 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz 100 28 42 34 41 20 19 20 9 -8 2 250 32 42 33 41 26 27 28 18 5 15 254
8 / 24 | Variable Air Volume Controllers OPTIMA-RES-A-125 ps LWA LW Non-Weighted Sound Power Level m3/h Pa dB dB(A) 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz 100 27 42 34 41 20 21 19 9 -7 2 250 32 43 36 42 26 29 27 19 5 15 398 Vmax @ 9 m/s * 243 88 Vmin @ 2 m/s * Air Flow 500 37 45 38 43 31 35 33 26 14 25 750 41 47 39 43 34 38 37 31 20 31 1000 43 48 40 44 36 41 39 34 24 35 100 26 36 18 35 20 22 23 14 <5 <5 250
-RC_VAVa Via Topology PE -WL-VAVa CYKY-J 3x1,5 500 V X:PE N L N L1 2002-433 3 XSU:1 1 1 2 ˜ 2 2 VAV-EHa M w 5 XEH:1 M U5 3 4 2002-474 24V AC ˜ 2 3 2002-479/011-000 2002-479/011-000 2002-479/011-000 24V AC 1 2 VAV-SUa WS-SUa /3 YSLCY 5x0,75 500 V 1 230V/24V, 30VA WS-VAV-EHa YSLCY 5x0,75 500 V 230V F1 T1A 3 U5 3 4 4 w 5 XEH:1 4 3 Feedback / MP-BUS supply 4 Feedback / MP-BUS extract -T1 XRC:1 G0 0V 2 G G -RC-a Flow control -WS-RC-a J-Y(St)Y 2x2x0,8 200 V 2
10 / 24 | Variable Air Volume Controllers Solutions for Room Controls with VAV Ventilation Systems The variable air flow controlled ventilation as a part of demand oriented control of room climate can be integrated in different ways according to various user requirements. The basic part of the climate control is the various room controllers. Each of them fits a different control solution at a corresponding cost level.
Variable Air Volume Controllers | 11 / 24 MZ3-Touch Ventilation Control Panel For VAV air flow control based on a single physical value like CO2 or VOC concentration. Functions The room controller can set the air flow volume on the VAV controller by the 0 V ... 10 V signal. The leading value for the control is the concentration of CO2 , eventually VOC in the air. For the measurement of this value, a separate transmitter shall be used with with a 0 V ... 10 V measurement signal.
12 / 24 | Variable Air Volume Controllers Topology 0 V . . . 10 V OPTIMA... VAV Controller 0 V . . .
Variable Air Volume Controllers | 13 / 24 EC-Basic – CO2 + Temperature Room Controller For VAV air flow control based on two physical values, temperature and CO2 concentration simultaneously. Functions The room controller can set the air flow volume on the VAV controller by the 0 V ... 10 V signal. The leading values for the control are the temperature (cooling mode or heating mode) and the concentration of CO2 in the air.
14 / 24 | Variable Air Volume Controllers Topology 0 V . . . 10 V OPTIMA...
Variable Air Volume Controllers | 15 / 24 RC-C3DOC Room Controller For VAV air flow control based on multiple physical values and control states in different configurable operation modes and sequences.
16 / 24 | Variable Air Volume Controllers The following control loop sequences can be configured on the RC: • Heating/Heating Neutral zone Output signal 100% 0% Heating 1 48% 52% Heating demand Heating 2 100% • Heating/Cooling Neutral zone Output signal 100% 0% Heating SP SP Room temperature Tr (°C) Cooling 100% • Heating/Cooling with VAV-control Neutral zone 100% Output signal Heating output Cooling output Increasing air flow on heating demand Max air flow on heating demand (settable)
Variable Air Volume Controllers • Cooling/Cooling Neutral zone Output signal 100% 0% Cooling 1 48% 52% Cooling demand Cooling 2 100% • Heating/Cooling/VAV Neutral zone Neutral zone 100% Y2 Y3 Output signal Y1 20% by default min . flow at cool output for VAV control 0% 100% . . . 0% 0% . . . 48% Controller output 52% . . .
18 / 24 | Variable Air Volume Controllers • Heating/Cooling/VAV simultaneaously with CO2 control Value with higher control difference becomes control value. Neutral zone Neutral zone 100% Y2 Y3 Output signal Y1 20% by default min . flow at cool output for VAV control 0% 100% . . . 0% 0% . . . 48% Controller output 52% . . .
Variable Air Volume Controllers • Heating/Cooling with forced ventilation Y3 = 100% at forced ventilation 100% Y1 Y2 Neutral zone Output signal Neutral zone 20% by default min . flow at cool output for VAV control 0% 100% . . . 0% 0% . . .
20 / 24 | Variable Air Volume Controllers • Full range change-over determined heating/cooling control by VAV combined with CO2 control 100 Cooling RC temperature control demand value (%) Heating Min Room temperature Tr (°C) Max Comparator, max .
Variable Air Volume Controllers | 21 / 24 Adjustment and indication of parameters The operation parameters, procedures and limits can be adjusted with the help of pushbuttons and indicated by the LCD display on the room controller. Adjustment and indication are also possible via PC with corresponding hardware and software. Communication The room controller has an RS485 on-board communication serial port for which the Modbus RTU or BACNet MS/TP bus communication protocols can be turned on.
22 / 24 | Variable Air Volume Controllers Installation, Maintenance & Operation Information about installation, maintenance and operation is available in the document “UserManual_OPTIMA-RES-A”. OPTIMA-RES-A is mounted on the wall or ceiling and is connected to a spiro duct by a rubber gasket tight connection. The system box can be fixed to the wall or ceiling by screws through the holes in four mounting ears on the bottom plate.
Variable Air Volume Controllers Related Products OPTIMA-R VAV Controller Air flow volume control units for standard air flow velocity range. Product information is available within the “DataSheet_OPTIMA-R” technical documentation and on Systemair DESIGN. OPTIMA-LV-R Low Velocity VAV Controller Air flow volume control units for low to medium air flow velocity range. Product information is available within the “DataSheet_OPTIMA-LV-R” technical documentation and on Systemair DESIGN.
www.systemair.com Systemair Production s.s.