TG K3

TG-K3...
-30...+30°C
-20...+10°C
0...30°C
0...60°C
20...50°C
40...70°C
Resistance
(kOhm)
Voltage
(V)
-30 -20 0 0 20 40 15.00 6.000
1 14.83 5.933
2 14.67 5.867
3 14.50 5.800
4 14.33 5.733
-20 -15 5 10 25 45 14.17 5.667
6 14.00 5.600
7 13.83 5.533
8 13.67 5.467
9 13.50 5.400
-10 -10 10 20 30 50 13.33 5.333
11 13.17 5.267
12 13.00 5.200
13 12.83 5.133
14 12.67 5.067
0 -5 15 30 35 55 12.50 5.000
16 12.33 4.933
17 12.17 4.867
18 12.00 4.800
19 11.83 4.733
10 0 20 40 40 60 11.67 4.667
21 11.50 4.600
22 11.33 4.533
23 11.17 4.467
24 11.00 4.400
20 5 25 50 45 65 10.83 4.333
26 10.67 4.267
27 10.50 4.200
28 10.33 4.133
29 10.17 4.067
30 10 30 60 50 70 10.00 4.000
Temperature resistance table
0...40°C
Resistance
(kOhm)
0 15.000
1 14.875
2 14.750
3 14.625
4 14.500
5 14.375
6 14.250
7 14.125
8 14.000
9 13.875
10 13.750
11 13.625
12 13.500
13 13.375
14 13.250
15 13.125
16 13.000
17 12.875
18 12.750
19 12.625
20 12.500
21 12.375
22 12.250
23 12.125
24 12.000
25 11.875
26 11.750
27 11.625
28 11.500
29 11.375
30 11.250
31 11.125
32 11.000
33 10.875
34 10.750
35 10.625
36 10.500
37 10.375
38 10.250
39 10.125
40 10.000
Resistance measurements can only be made when the
sensor is not connected to a controller.
Voltage measurements are made on the sensor input
when the sensor is connected to a controller. This value
is valid for controllers AQUA24A1(2,3)(F)/D and
AQUA24(230)TF/D.
Sensor with NTC-element for measuring air temperature
in ventilation ducts.
TG-K3... is intended for use with the Aqualine, PULSER,
TM, TTC and Floorigo ranges. The sensor has adjustable
insertion length and is delivered with 1.5 m cable.
TG-K3...
Duct sensor
revision
07 2010