Modbus Registers OPTIMA...GOMOD
Short instruction 227VM-024-05-MB 
Written by: Michael Köhle    Date: 13.11.2014 08:56:00  Side 7 of 13
2.1.2.  Holding register customer (parameter table) 
-r functions-code 0×03h -w functions-code 0×06h 
Name 
Address 
decimal  Data typ 
Value 
range  r/w  Description 
memory 
def. 
value 
Set point  0  WORD  0…10000  r/w  Set point [%] 0 ..100.00 
see register 122: 
'0': set point is read only 
RAM 
Override 
control 
1  WORD  0…4  r/w  Override control 
'0’ - - - 
'1’ open 
'2‘ close 
'3' min 
'4' max 
RAM 
Com-
mand 
2  WORD  0…4  r/w  Command 
'0’ - - - 
'1’ adaption 
'2‘ - - - 
'3' - - - 
'4' controller reset 
RAM 
Device ID  3  WORD  0..3  r  Device ID 
'0’ - - - 
'1’ standard actuator 
'2‘ VAV 
'3' fire damper 
EEPROM 
2 
Relative 
position 
4  WORD  0…10000  r  Relative position [%] 0 .. 
100.00 
65535 = this function is not 
supported 
RAM 
Absolute 
position 
5  WORD  0…65000  r  Absolute position [°] [mm] 0 .. 
650.00 
65535 = this function is not 
supported 
RAM 
Relative 
flow 
6  WORD  0…10000  r  VAV flow [%] 0 .. 100.00  RAM 
Absolute 
flow 
7  WORD  0…65535  r  VAV flow [m³/h][l/s][pa]  RAM 
sensor 
value 1 
8  WORD  [°C] 
0...65535 
[mV] 
0…10000 
r  *external sensor value 
[Ω] 0 .. 10000 
[mV] 0 ..10000 
*only supported on hardware 
with sensor inputs. 
RAM 
sensor 
value 2 
(optional) 
9  WORD  [°C] 
0..65535 
[mV] 
0..10000 
r  *external sensor value 
[Ω] 0 .. 10000 
[mV] 0 ..10000 
*only supported on hardware 
with sensor inputs. 
RAM 
analog 
output 
(optional) 
10  WORD   [mV] 
0…10000 
r/w  analog output 
 [mV] 0 ..10000 
 see register 122 
RAM 
digital 
output 
(optional) 
11  WORD   [-] 
0…1 
r/w  *digital output 
0 ..1 
*only supported on hardware 
with digital output. 
RAM 