RH CO2 Temperature sensor manual

Page 4

Power Consumption
Typical 0.7 W at nominal voltage of 24V AC RMS
Temperature Dependence
0.2% FS per °C (±0.11% per °F)
Stability
Single Channel
<2% of FS over life of sensor (15 years)
Pressure Dependence
0.135% of reading per mm Hg
Certifications
CE and RoHS compliant
Signal Update
Every 5 seconds
CO
2
Warm-up Time
< 2 minutes (operational)
10 minutes (maximum accuracy)
Operating Conditions
32°F to 122°F (0°C to 50°C)
0 to 95% RH, non-condensing
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Flammability Classification
UL94 5VA
Temperature Measurement
RTD– Class ??
RH Sensing Element
Capacitive polymer sensor
RH Range
0% to 99% RH (non-condensing)
RH Accuracy (25°C)
±2.5% RH (20 to 80% RH)
±3.5% RH (<20% and >80% RH)
Active Temperature Accuracy
±0.8°C @ 22°C
Active Temperature Range
0 to 50°C
ABC Logic™ Self Calibration System
ABC Logic™ (Automatic Background Calibration) self calibration
allows the sensor to continually recalibrate itself when the indoor
concentrations drop to outside levels while the building is unoccupied.
Generally a building must be regularly unoccupied for 4 hours or more
for this self-calibration system to operate properly. Under these
conditions, ABC Logic™ should maintain sensor calibration over the
lifetime of the sensor. The ABC Logic™ should be turned OFF where a
building is continuously occupied 24 hours per day, or where there could
be significant sources of non-occupant related CO
2
such as greenhouses,
breweries and other industrial and food processing applications.
Output
Analog
0 to 5 V, (100 output impedance)
0 to 10 V (100 output impedance) and
4 to 20mA (R
L
maximum 500 ) available simultaneously for CO
2
output
Digital to analog error ±1%