1&2 Installation manual

T63361-001
Oct 2012
Page 2 of 3
Page 2 Systemair CO2 Duct Mount Sensors
Specifications
Temperature: 0ºC to 50ºC (32ºF to 122ºF)
Humidity: 0 to 95% relative humidity, non-condensing
0-2000 PPM factory calibrated
Storage Conditions
-40ºC to 70ºC (-40ºF to 158ºF)
Duct Air Velocity
0 to 1500 ft/min (0 to 450 meter/min)
Output
Voltage 0 to 10 VDC; 0 to 2000 ppm CO (100 ohm output impedance)
Power Supply Requirements
18 to 30 VAC RMS, 50/60 Hz or 18 to 42 VDC, polarity protected.
Power Consumption
Temperature Dependence
2
Stability
<2% of full scale over the life of the sensor (10 years typical)
*Accuracy
Typical values (1.65 watts peak, 0.65 watts avg.@ 42 VDC)
certified reference
*Note: The product line offers patented ABC Logic™ software
for self correction of drift to better than ±20 ppm per year. The system is
virtually free of maintenance and typically has a lifetime of more than 10
years.
<1% of full scale @ 22ºC (72ºF)
0.2% of full scale per ºC
±40 ppm +3% of reading @ 22ºC (72ºF) when compared with a factory
Non-linearity
Physical Requirements
Pressure Dependence
Dimensions:
0.13% of reading per mm of mercury
Probe Length: Systemair-1 CO2 duct sensor 4.09 in (10.38 cm)
Systemair-2 CO2 duct sensor 8.07 in (20.51 cm)
Probe Diameter: 1.24 in (3.15 cm)
Junction Box Depth: 1.58 in (4.02 cm)
Junction Box H x L: 3.05 in x 3.05 in (7.46 cm x 7.46 cm)
Color: Grey (GY6275)
turned on.
Installation Kit
Response Time
Included with the transducer are wire nuts, mounting screws and
installation instructions.
Sampling Rate
Every two seconds
Warm-up Time
*Calibration
Sensors will be calibrated at zero and span at the factory. Calibration in
the field will not be required. Sensors will be shipped with ABC Logic™
Three minutes typical for a 90% step change at low duct speeds
< two minutes (operational); 10 minutes to achieve maximum accuracy
Certifications
RoHS compliance
FCC Part 15,B
CE EMC EN61000-6-2
EN61000-6-3
Enclosure flammability rating UL94-5VA