34/40 | User Manual S-SA2 & S-SA2L | 201905
Fig. 58: G230 connection scheme; actuator GRUNER Fig. 59: G24 connection scheme; actuator GRUNER
NOTES:
• Caution! Main power supply voltage!
• Parallel connection of several actuators possible.
• Power consumption and switching thresholds must be observed!
• Connect power supply to wire 1+2, actuator drives to position OPEN (1).
Is also wire 3 connected to the power supply, actuator drives to position CLOSED (0).
Fig. 60: Parallel connection of two coupled GRUNER actuators on one Smoke damper
NOTES:
• Caution! Main power supply voltage!
• Supply via isolation transformer.
• Power consumption and switching thresholds must be observed!
• Connect power supply to wire 1+2, actuator drives to position OPEN (1).
Is also wire 3 connected to the power supply, actuator drives to position CLOSED (0).
S1 S2 S3 S4 S5 S6
<5°
<85°
1
N
2 3
LL
AC 230 V
S1 S2 S3 S4 S5 S6
<5°
<85°
1
2 3
–
+
⊥ ~
+
~
AC/DC 24 V
S1 S2 S3 S4 S5 S6
<5°
<85°
1
2 3
S1 S2 S3 S4 S5 S6
<5°
<85°
1
2 3
–
+
⊥ ~
LLN
+
~
AC/DC 24 V (G24)
AC 230 V (G230)