UserManual S SA2 S SA2L202010

6/40 | User Manual S-SA2 & S-SA2L | 201905
Installation Methods
All S-SA2 and S-SA2L smoke dampers are CE certied according to EN 12101-8:2011, tested according
to EN 136610 :2011+A1:2017, and classied according to EN 13501-4:2016.
The smoke damper, together with its installation, form an inseparable part of the re resistivity rating.
Tab. 1: S-SA2 re resistivity
Dimension
Range
(mm)
Certicate
No.
Product
Type
Classication
Supporting
Construction
Construction Type/Minimal Thickness (mm)
Wet Soft
200 × 200
up to
1000 × 800
1396 - CPR - 0112
S-SA2
EI90 (v
ew
i ↔ o) S1500
C
mod
AAmulti
ve
Rigid/150
Flexible/150
Rigid/150
Flexible/150
200 × 200
up to
1600 × 1000
EI120 (v
ew
i ↔ o) S1500
C
mod
AAmulti
ve -
EI120 (h
ow
i ↔ o) S1500
C
mod
AAmulti
ho Rigid/150 -
Allowed Blade Axis Orientation
Dimension
Range
(mm)
Certicate
No.
Product
Type
Classication
Supporting
Construction
Applicable Duct Tested per Standard
On the Duct/
Bottom Mounted
On the Duct/
Top Mounted
On the Duct/
Side Mounted
In the Duct/
Horizontal
Axis
200 × 200
up to
1600 × 1000
1396 - CPR - 0147
S-SA2L
EI120 (v
ed
i ↔ o) S1500
C
mod
AAmulti
ve
EN 1366-9,
EN 1366-8
EN 1366-9,
EN 1366-8
EN 1366-9,
EN 1366-8
-
EI120 (h
od
i ↔ o) S1500
C
mod
AAmulti
ho - -
EN 1366-9,
EN 1366-8
-
Allowed Blade Axis Orientation
Tab. 2: S-SA2L re resistivity