PCA 2 1000D OPERATING INSTRUCTION25055055

Outside-temperature dependent target-setpoint
S1 Setpoint1
S2 Set Internal2
P-min. Min. Setpoint
T-min Min. temperature
T-Start Setpoint reducing will start below this outside
temperature
T-band Temperature range
AT Outdoor temperature
An outside temperature compensa-
tion can be activated (sensor con-
nection terminals "TF-"TF") when
being operated as a pressure con-
trol device.
This function automatically
changes the set and active Set-
point 1 or Setpoint 2 proportional
to the measured outdoor tempera-
ture (see INFO: SETPOINT CON-
TROL).
30.0 K
(54.0 °F)
T-Band SA
Temperature range setpoint lowering
Temperature range in which the setpoint change continiously
with outdoor temperature.
Setting range: 0.0...100.0 K (0.0...180.0 °F)
Factory setting: 30.0 K (54.0 °F)
15.0 °C
(59.0°F)
T-Start SA
Start temperature for setpoint lowering
Setpoint reducing will start below this outside temperature.
Setting range: -10.0...40.0 °C (14.0...104.0 °F)
Factory setting: 15.0 °C (59.0 °F)
500 Pa
Min. Setpoint
(2.0 in.wg)
Minimum setpoint
Minimum pressure for very low outside temperature.
Setting range: in measuring range of sensor
Factory setting: 500 Pa (2.0 in.wg)
(xxx) Values for Imperial units (US)
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
21/48