PCA 2 1000D OPERATING INSTRUCTION25055055

Possible controls
Real input Inverting DI State input active
Digital input D1 (terminals: 1, 2)
OFF
Voltage ON
Setpoint 2
Voltage OFF
Setpoint 1
ON
Voltage ON
Setpoint 1
Voltage OFF
Setpoint 2
Timer from time switch
OFF
Timer active
Setpoint 2
Timer not active
Setpoint 1
ON
Timer active
Setpoint 1
Timer not active
Setpoint 2
MODBUS interface
(terminals: A, B)
OFF
Register H01 Bit 15 not set
Setpoint 1
Register H01 Bit 15 set
Setpoint 2
ON
Register H01 Bit 15 not set
Setpoint 2
Register H01 Bit 15 set
Setpoint 1
8.5 Menu group "LIMITS"
8.5.1 Limit message modulation
Menu overview
Function Designation
OFF
Level Fuction
OFF: no function
ON: limit message active
The Limit Uout message appears in the display if the set
limit value for modulation is exceeded. The message via the
relay depends on the programmed function (see IO Setup),
with the factory setting (K1 function =
|
2K
|
, not inverted) the
relay is de-energised (terminals 13 - 14 disconnected).
0.0 V
Level min.
If the modulation exceeds the set Level max. value, this is
reported until the set value Level min. has been undercut.
Setting range Level min.: 0...10 V
Setting range Level max.: 10...0 V
10.0 V
Level max.
2 s
Level delay
The indication is delayed by the time set.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.