1.3.4 Diagnostics
Command code: 0x08
This command is used to check the MODBUS function
Command from master:
The following data bytes are transmitted:
MSB subfunction code
LSB subfunction code
1 - 17 data bytes
Only subfunction code 0000 is supported!
Response from fan:
The following data bytes are transmitted:
MSB subfunction code
LSB subfunction code
1 - 17 data bytes
Exception codes:
In case of error, only one data byte (the exception code) will be transmitted
Exception codes:
0x01: Subfunction code not supported (≠ 0000)