MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 32 of 70
Form 1003
2.8 Operating minutes counter
Address : D00A
D181 (alternative)
Write authorisation : ebm-papst
Encoding:
bytes Data[h] minutes Operating
After every full minute the fan runs, the operating minutes counter increases by 1.
To maintain compatibility with MODBUS 5.0 (non-Lite version), the operating minutes counter can be
addressed via the address D009 as well as via D181.
We recommend D00A.
2.9 Fan address
Address : D100
Write authorisation : ebm-papst, customer, end customer
Encoding:
(LSB) bytes Dataaddress Fan
The MSB is of no relevance!
Permitted value range: 1 to 247