MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 33 of 70
Form 1003
2.10 Source set value
Address : D101
Write authorisation : ebm-papst, customer, end customer
Encoding:
This parameter specifies the source from which the set value is taken:
Value
Source set value
0
Analogue input 0 to 10 V
1
RS485 (default set value parameter D001)
The MSB is of no relevance!
Permitted value range: 0 to 1
2.11 Preferred running direction
Address : D102
Write authorisation : ebm-papst, customer, end customer
Encoding:
This parameter specifies the preferred running direction.
Value
Preferred running direction
0
anti-clockwise
1
clockwise
The MSB is of no relevance!
Permitted value range: 0 to 1
After this parameter is written, the new value becomes applicable immediately (no reset necessary).
If the fail safe function is activated and a break in the MODBUS connection is detected, the direction of
rotation is set to the value of "Fail safe function running direction" (see 2.38). The parameter Preferred running
direction is not relevant then.