speed controllers are no longer controlled. This means that all
fans stop!
5.4 Digital input (D1)
Different functions can be assigned to the digital input D1(see IO
SETUP).
A voltage at terminals “1” and “2” (10...24 V DC) activates the
programmed function (note polarity - see connection diagram).
5.5 Relay outputs “K1”
The relay output “K1”can have different functions assigned to it,
see IO SETUP. Max. contact rating see technical data and con-
nection diagram.
Function fault indication (factory setting) for “K1”:
•
For operation the relay is energized, connections “13” and “14”
are bridged. For fault the relay is de-energized.
•
When switching off via enable (see IO SETUP/Digital inputs
"DI"), the relay remains energized.
5.6 RS-485 interface for MODBUS
The device comes equipped with a RS-485 interface for network-
ing via MODBUS. Conntection at: “A (D+)”, “B (D-)” and “GND”.
11.03.2014
v_am_modbus_connect.vsd
ID1 GND
A
(D+)
B
(D-)
ID2GND
A
(D+)
B
(D-)
B
(D-)
ID1 GND
A
(D+)
B
(D-)
ID2GND
A
(D+)
MODBUS
(RS-485)
MODBUS
(RS-485)
Addressing
Addressing
MODBUS
(RS-485)
MODBUS
(RS-485)
Addressing
Addressing
The connections for MODBUS “A (D+)”, “B (D-)” are available double on the module and are
connected with each other internally.
Information
•
You must ensure correct connection; i.e. “A (D+)” must also be
connected on the following devices to “A (D+)”. The same
applies to “B (D-)”.
•
In addition, a "GND" connection must be established, as
Operating Instructions PCA-2 1000D2 Electrical installation
L-BAL-E295-GB 1906 Index 001 Part.-No.