PCA 2 1000D OPERATING INSTRUCTION25055055

Mode Function
5.02
Volume ow control (PID) with outdoor temperature compensation:
output 0...10 V depending on adjusted setpoint, outdoor temperature
and measured actual value.
7.2 Start-up
Procedure
1. You must mount and connect the device in accordance with
the operating instructions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating
plate.
4. Set the mode, unit and measuring range and adjust the sensor
in the BASE SETUP.
5. Set the parameters for control operation for the modes
4.01 ,
4.02 , 5.01 , 5.02 unter "SETTING".
7.3 Menu structure
100 Pa
Δp
Display after turning on the voltage supply.
Switch over between actual value display and
INFO with the key shortcut for Escape (Esc
= + ).
INFO
Selection of the menu group (e.g. BASE SETUP) to the right
through the -key, to the left through the -key.
Youcangotothemenuitemsinthemenugroups (e.g. mode) by using
the P key. Use the arrow keys to move up and down within the
menu group.
To make adjustments, press the P key after selecting the menu
item. If the previously set value starts to ash, it can be adjusted
with the + keys and then saved with the P key. To exit the
menu without making any changes, use the Esc short-key, i.e.,
the originally set values remain.
Operating Instructions PCA-2 1000D2 Modes/Start-up
L-BAL-E295-GB 1906 Index 001 Part.-No.
17/48