PCA 2 1000D OPERATING INSTRUCTION25055055
Table Of Contents
KTY81-210
Temp. Sensor
Temperature sensor for recording the outdoor temperature in
4.02 operating mode. Sensor type: KTY 81-210 (factory fit-
ted) or PT 1000.
0...1000 Pa
Measuring
range
1: 0...1000 Pa (0...4.0 in.wg)
2: 0...500 Pa (0...2.0 in.wg)
3: 0...300 Pa (0...1.2 in.wg)
4: 0...200 Pa (0...0.8 in.wg)
Adjustable measuring range
OFF
Autozero
If the actual value is not “0 Pa Δp” in pressureless state a
zero-point adjustment is possible with fuction “Autozero”.
This may be necessary, for example, in case of heavy ther-
mal fluctuations in the sensor environment or non-vertical
mounting.
Proceed as follows:
1. Pull off the pressurised hoses.
2. Switch function “Autozero” to “ON”.
3. The display switches to the actual value display and the
value “0” is displayed after zero point calibration has
taken place.
4. The necessary difference up to “0” is displayed in the
BASE SETUP under “Offset”.
0 Pa
(0.000 in.wg)
Offset
Alternatively to the automatic zero point calibration, the offset
value can also be set manually.
Setting range: +/ - 1000 Pa (+/- 4.000 in.wg)
0.0 K
(0.0 °F)
Offset
Offset temperature sensor for mode
4.02 .
Setting range: -20.0...20.0 °C (-36.0...36.0 °F)
Factory setting: 0.0 K (0.0 °F)
OFF
Factory Setting
Attention!
ON => restore factory setting = delivery status
(xxx) Values for Imperial units (US)
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
19/48