PCA 2 1000D OPERATING INSTRUCTION25055055

Air ow measuring range: max. 65000 m
3
/h (38257 cfm) depend-
ing on setting of measuring range and K-Factor.
8.2.3 Setting for operation
5.01 and 5.02
SETTING
1185 m
3
/h
(697 cfm)
Setpoint 1
Setpoint1
Setting range: depending on measuring range of sensor and
K factor
Factory setting: 1185 m
3
/h
1185 m
3
/h
(697 cfm)
Setpoint 1
Set Internal2
Setting range: depending on measuring range of sensor and
K factor
Factory setting: 1185 m
3
/h
1185 m
3
/h
(697 cfm)
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable
control
Setting range: in measuring range of sensor
Factory setting: 1185 m
3
/h
0.0 V
Min. Uout
Minimal output voltage
Setting range: 0...10 V (priority over "Max. Uout")
Factory setting: 0 V
10.0 V
Max. Uout
Maximal output voltage
Setting range: 10...0 V
Factory setting: 10 V
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
24/48