PCA 2 1000D OPERATING INSTRUCTION25055055

Example message by relay K1:
not inverted
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
Inverting
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
min max 100 %
A
0
1
minmax 100 %
0
1
11.05.2007
v_grenzwert_ausst_k1_ni.vsd
A
A Modulation
min max 100 %
0
1
minmax 100 %
0
1
11.05.2007
v_grenzwert_ausst_k1_i.vsd
A
A
A Modulation
If "Level min." is higher than "Level max." , the "Level max." switching point is
without hysteresi.
8.5.2 Limit message actual value
Menu overview
Function Designation
OFF
Actual Value
Fnc
OFF: no function
ON: limit message active
The values "Value min." and "Value max." can be set inde-
pendently of one another. The unit depends on the selected
operating mode (
4.. / 5.. ) and unit (metric / inch).
Depending on the operating mode, the message "Limit Pres-
sure" / "Limit AirVolume" appears in the display if the set limits
for the actual value are exceeded or not reached.
The message via the relay depends on the programmed
function (see IO Setup), with the factory setting (K1 function =
|
2K
|
, not inverted), the relay is de-energised in case of a
message (terminals 13 - 14 disconnected).