PCA 2 1000D OPERATING INSTRUCTION25055055

8.5.3 Limit message outdoor temperature
Function is only available in operating modes
4.02 and 5.02 .
Menu overview
Function Designation
OFF
Actual Temp
Fnc
OFF: no function
ON: limit message active
The values "Temp min." and "Temp max" can be set inde-
pendent of each other.
The "Limit Temp." message appears in the display if the set
limits for the outdoor temperature are exceeded or not
reached.
The message via the relay depends on the programmed
function (see IO Setup), with the factory setting (K1 function =
|
2K
|
, not inverted), the relay is de-energised in case of a
message (terminals 13 - 14 disconnected).
-50.0 °C
(-58.0°F)
Temp min.
Work can be carried out with one as well as with both limit
indicators.
If the actual value undercuts the set value "Temp min.", this is
reported until the set value (plus 5 % hysteresis) has been
exceeded once again.
If the actual value exceeds the set value "Temp max.", this is
reported until the set value (minus 5 % hysteresis) has been
undercut once again.
150.0 °C
(302.0°F)
Temp max.
2 s
Temp delay
The indication is delayed by the time set.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Information
Always set the value for "Temp max." higher than the value for
"Temp min.".
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.