PCA 2 1000D OPERATING INSTRUCTION25055055

8.7 MODBUS SLAVE
8.7.1 Address and interface parameters
Addressing and conguration of the MODBUS Slave interface.
Via this interface the device can be networked with a master
building control system, the device then operates as a pure Slave
and uses the MODBUS-RTU protocol.
The connection is made to the terminals A (D+), B (D-) of the
MODBUS Slave interface (see installation / RS-485 interfaces for
MODBUS RTU).
Menu overview
Function Designation
247
Bus Address
Bus Address
The device address is factory set to the highest available
MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
19200
UART Baudrate
UART Baudrate
Setting transfer rate
Valid values: 4800, 9600, 19200, 38400, 115200
Factory setting: 19200
8E1
UART Mode.
UART Mode
Setting transfer format
Valid values: 8N1, 8O1, 8E1, 8N2
Factory setting: 8E1
Information
The MODBUS settings for baud rate and UART mode are only
applied after a restart - to do this disconnect the voltage supply.