PCA 2 1000D OPERATING INSTRUCTION25055055

HR
Mode
Function/Setting4. 5.
00 01 02 00 01 02
H42
x
x
Start temperature setpoint lowering:
-100...400
-10.0...40.0 °C (-140...1040
14.0...104.0 °F)
H43
x
x
Minimum Setpoint: 0...max. measuring range (Pa,
in.wg, m
3
/h, cfm)
H44 x x x x x x
Units of the display: 0 = SI units "metric", 1 = Imperial units
(US) "inch"
H45 x x x x x x
Measuring range: 0/1/2/3
:
200/300/500/1000 Pa (0.8/1.2/2.0/4.0 in.wg)
H46
x
x
Temperature sensor type: 0 = KTY 81-210, 1 = PT 1000
H47 x x x x x x
Automatic zero point adjustment pressure sensor: 0 =
OFF, 1 = AutoZero
H48 x x x x x x
Manual offset pressure sensor: +/-1000 (Pa), (+/- 4.000
(in.wg))
H49
x
x
Offset temperature sensor:
-200...200
-20.0...20.0 °C (-360...360
-36.0...36.0 °F)
H51
x x
x x
Time: HIGHBYTE = hours, LOWBYTE = minutes
H52
x x
x x
Date: HIGHBYTE = month, LOWBYTE = day
H53
x x
x x
Year: 0...99
2000...2099
H54
x x
x x
Automatic summer time: 0 = OFF, 1 = ON
H56
x x
x x
Turn-on time: HIGHBYTE = hours, LOWBYTE = minutes
H57
x x
x x
Turn-off time: HIGHBYTE = hours, LOWBYTE = minutes
* For bit-by-bit activation: Bit 15 = lowest value bit, Bit 0 = highest value bit
Information
The registers HR00, HR01, HR02, HR47, HR51, HR52 and HR53
can be written as often as needed. For all other registers, write
processes are limited to 10,000 (i.e. only use them for cong-
uration purposes).
Value of the bits
MSB LSB
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15
0x8000 0x4000 0x2000 0x1000 0x0800 0x0400 0x0200 0x0100 0x0080 0x0040 0x0020 0x0010 0x0008 0x0004 0x0002 0x0001
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.