PCA 2 1000D OPERATING INSTRUCTION25055055

8.7.2.2 Input register
IR
Mode
Information
4. 5.
00 01 02 00 01 02
I00 x x x x x x
Software version: 100 = 1.00
I01 x x x x x x
Product code: 0h0508
I03 x x x x x x
Unique device Signature 0...5
I04 x x x x x x
Unique device Signature 0...5
I05 x x x x x x
Unique device Signature 0...5
I06 x x x x x x
Unique device Signature 0...5
I10
x x
x x
Operation status bit wise* for DI1-DI3, relay and timer:
b15 = Timer, b14 = relay K1, b7 = DI1, b6 = DI2, b5 = DI3
I12 x x x x x x
Device status decimal:
0 = no Error
1 = Enable
2 = Limit output voltage
3 = Limit actual value pressure
4 = Limit actual value volume ow
5 = Limit actual value temperature
6 = temperature sensor defect
7 = Pressure sensor defect
I23 x x x x x x
Actual value temperature: -500...1500
-50.0...150.0 °C
(-400...3020
-40.0...302.0 °F)
I26
x x x
Actual value pressure: 0... max measuring range (Pa,
in.wg)
x x x
Actual value volume ow: 0... max measuring range (m
3
/h,
cfm)
I27 x x x x x x
Actual value output voltage: 0...100
0...10 V
I28
x x
x x
Current Setpoint
* For bit-by-bit evaluation: Bit 15 = lowest value bit, Bit 0 = highest value bit
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
44/48