3 Product overview
3.1 Function
Sensor-control module with differential-pressure sensors in proven
ceramic-cantilever technology for climate and clean-room applica-
tion.
The pressure range goes from 0...1000 Pa (0...4.0 in.wg), four
measuring ranges are programmable.
Function when the pressure at the Plus- connection exceeds the
pressure at the Minus- connection.
Depending on the programmed Mode the device can be used
as sensor or as a control module for pressure or volume ow.
For operation as pressure sensor the device supplies an output
signal (0...10 V) proportional to the measuring range.
For operation as volume ow sensor the device supplies an
output signal (0...10 V) proportional to the air volume measuring
range (see INFO / Range qV). Function in combination with
centrifugal fans and measuring device in the inlet ring. The
controller calculates the volume ow of the fan from the K-
Factor and pressure differential between the suction side and
the inlet duct.
For operation as control module for pressure or volume ow the
purpose of the device is to reach and maintain the target value
set. To accomplish this, the measured actual value (sensor
value) is compared with the adjusted target value, and the con-
trolled value is deduced from this. Controlled output (0...10 V)
e.g. for activating a speed controller for fans or an EC-fan
directly.
Operating Instructions PCA-2 1000D2 Product overview
L-BAL-E295-GB 1906 Index 001 Part.-No.