MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 34 of 70
Form 1003
2.12 Save set value
Address : D103
Write authorisation : ebm-papst, customer, end customer
Encoding:
This parameter specifies whether or not an incoming default set value (D001) is also stored in the EEPROM
under set value (EEPROM) (D114 / D115).
Value
Function
0
Set value is not stored
The fan is stationary after a reset
1
Set value is stored in EEPROM
After reset, the fan will run with the stored set value
The MSB is of no relevance!
Permitted value range: 0 to 1
The function must not be activated if the default set value is repeatedly write-accessed at
frequent intervals (D001, see 2.3 Default set value)!
If this instruction is not observed, there is a risk that the memory will be permanently
destroyed.
If the function is activated, the maximum number of times the default set value can be write
accessed over the entire service life of the fan is 100,000.
For more information, see the fan data sheet.
2.13 Internal parameter set
Address : D105
Write authorisation : ebm-papst, customer, end customer
Encoding:
This parameter specifies whether parameter set 1 or parameter set 2 is used.
Value
Parameter set
0
Parameter set 1
1
Parameter set 2
The MSB is of no relevance!
Permitted value range: 0 to 1
After this parameter is written, the new value becomes applicable immediately (no reset necessary).