PCA 2 1000D OPERATING INSTRUCTION25055055

Example for Mode 4.01 (Factory setting)
INFO
SETTING
BASE SETUP
P Esc
P Esc
P Esc
100 Pa
Δp
100 Pa
Setpoint 1
4.01
Mode
100 Pa
Setpoint 1
100 Pa
Setpoint 2
1: metric
Units
Reprogramming Mode
4.01 to 5.00 in BASE SETUP
1 2 3 4 5 6 7
4.01
Mode
P
«4.01»
Mode
«5.00»
Mode
P
5.00
Mode
8 Programming
8.1 Pressure sensor
4.00 and pressure control 4.01 +
4.02
8.1.1 Base setup 4.00 ... 4.02
BASE SETUP
4.01
Mode
4.00 : Pressure sensor
4.01 : Pressure control (factory setting)
4.02 : Pressure control with outdoor temperature compensa-
tion
metric
Units
Display in SI units "metric" (factory setting) or Imperial units
(US) "inch".
Conversion factors:
Pressure: 1.0 in.wg = 254 Pa
Temperature (
4.02 ) t / °F = 1.8 x t °C + 32
Settings for temperature differences (with SI units in K) are
also made for Imperial units (US) in °F ( Δ 1.8 °F
Δ 1 K ).
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
18/48