PCA 2 1000D OPERATING INSTRUCTION25055055

KTY81-210
Temp. Sensor
Temperature sensor for recording the outdoor temperature in
4.02 operating mode. Sensor type: KTY 81-210 (factory t-
ted) or PT 1000.
0...1000 Pa
Measuring
range
1: 0...1000 Pa (0...4.0 in.wg)
2: 0...500 Pa (0...2.0 in.wg)
3: 0...300 Pa (0...1.2 in.wg)
4: 0...200 Pa (0...0.8 in.wg)
Adjustable measuring range
OFF
Autozero
If the actual value is not 0 Pa Δp in pressureless state a
zero-point adjustment is possible with fuction Autozero.
This may be necessary, for example, in case of heavy ther-
mal uctuations in the sensor environment or non-vertical
mounting.
Proceed as follows:
1. Pull off the pressurised hoses.
2. Switch function Autozero to ON.
3. The display switches to the actual value display and the
value 0 is displayed after zero point calibration has
taken place.
4. The necessary difference up to 0 is displayed in the
BASE SETUP under Offset.
0 Pa
(0.000 in.wg)
Offset
Alternatively to the automatic zero point calibration, the offset
value can also be set manually.
Setting range: +/ - 1000 Pa (+/- 4.000 in.wg)
0.0 K
(0.0 °F)
Offset
Offset temperature sensor for mode
4.02 .
Setting range: -20.0...20.0 °C (-36.0...36.0 °F)
Factory setting: 0.0 K (0.0 °F)
OFF
Factory Setting
Attention!
ON => restore factory setting = delivery status
(xxx) Values for Imperial units (US)
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
19/48