MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 40 of 70
Form 1003
2.22 Minimum permissible modulation level
Address : D118
Write authorisation : ebm-papst
This parameter defines the lower limit for the minimum modulation level (see 2.17 Minimum modulation level).
Encoding:
%100
256
[%]
bytes Data
level modulation perm. Min.
The MSB is of no relevance!
If too small a value is selected for this parameter (especially values < 8%), the motor may shut down with the
error "Locked motor"!
2.23 Maximum speed
Address : D119
Write authorisation : ebm-papst, customer
This parameter has two functions:
All parameters with speed information (set values, actual values) are based on this value.
The value 64,000 in this speed information corresponds to the maximum speed value given here.
In the "open-loop PWM control" mode, the speed is limited to the value given here. (In closed-loop speed
control, the speed is controlled in any event.)
Encoding:
bytes Datarpm speedMax. ][
The maximum speed is made up of 2 bytes.
Limitation:
Maximum speed < Maximum permissible speed (see 2.24 Maximum permissible speed)