MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 69 of 70
Form 1003
3.19 Sensor actual values
Address of actual sensor value : D01B
Address of actual sensor value 1 : D023
One sensor can be connected to the fan.
Actual sensor value and actual sensor value 1 outputs the actual value of the external sensor at analog input
("set value input").
Encoding:
V
byteData
VvalueActual 10
65536
][
)10
65536
(
)()]([
V
byteData
Rg
URgRgunitvalueActual
Actual value [V] = output voltage of sensor
Rg (U) = characteristic of sensor depending on voltage
A sensor can only be connected to measure and display the sensor actual value.
Closed-loop control based on the sensor signal is not possible.. Control mode „Closed-loop sensor control“ is
not supported (see 2.14)
3.20 Current parameter set
Address : D01D
This parameter specifies which parameter set (1 or 2) is currently in use.
The value of the "Internal parameter set" is always shown here (see 2.13 Internal parameter set).
Encoding:
Value
Parameter set
0
Parameter set 1
1
Parameter set 2