2.29.2 Maximum permitted power
Address for maximum permitted power : D135
Write authorisation : ebm-papst
Encoding:
][][
256
][max, AIzeferenceRVUzeferenceR
bytes Data
WpermP
P max, zul ............ Maximum permitted power
Ref. Uz ................. Reference variable DC-link voltage (see 2.43 Reference value of DC-link voltage).
Ref. Iz ................... DC-link current reference variable (see 2.44 Reference value of DC-link current)
The MSB is of no relevance!
This parameter defines the upper limit for the maximum power (see 2.29.1) and the maximum power at
derating end (see 2.29.3).
2.29.3 Power derating
Address for maximum power at derating end : D136
Address for module temperature power derating start : D137
Address for module temperature power derating end : D138
Address for motor temperature power derating start : D14D
Address for motor temperature power derating end : D14E
Write authorisation : ebm-papst, customer
Depending on the module temperature (see 3.13 Module temperature) and the motor temperature (see 3.14
Motor temperature), the maximum power decreases based on the following curve. Each temperature can
have its own defined curve.
P max
P max DE
TModul_DS
TModul_DE
T [°C]
Max. power [W]
TMotor_DS
TMotor_DE
Max. power depending on motor temperature
Max. power depending on module temperature
P max ........................... Maximum power
P max DE .................... Maximum power at derating end
TModul_DS .................. Module temperature at start of derating
TModul_DE .................. Module temperature at end of derating
TMotor_DS ................... Motor temperature at start of derating