This process is continued until the number of attempts specified in the "Number of startup attempts" is
reached. If this also does not succeed in getting the fan rotating, the "Locked motor" error message (see 3.9
Motor status) is generated. During additional startup attempts, the modulation level is returned to the value
defined in the parameter "Starting modulation level" and not increased any more.
2.34 Relay dropout delay
Address : D153
Write authorisation : ebm-papst, customer, end customer
In the event of a fault, the relay drops out after a delay equal to the time specified here.
Encoding:
bytes Datasdelay dropoutRelay ][
The MSB is of no relevance!
2.35 Fail safe function on/off
Address : D15C
Write authorisation : ebm-papst, customer
Encoding:
This parameter specifies whether the fail safe function is active or inactive.
Value
Fail safe function
0
Inactive
1
Active
The MSB is of no relevance!
Permitted value range: 0 to 1