MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 66 of 70
Form 1003
3.10 Warning
Address : D012
A warning is a stage preliminary to an error message, i.e. the limit value for the error message has almost
been reached.
Encoding:
A set bit makes the warning active:
MSB
LRF
UeHigh
nGrenz
UzHigh
0
Cable
break
n_Low
0
LSB
Brake
UzLow
TEI_high
TM_high
TE_high
P_Limit
0
I_Limit
LRF : Shedding function active (see 2.33 Shedding function)
UeHigh : Supply voltage high
nGrenz : Limiting speed exceeded
UzHigh : DC-link voltage high
Cable break : cable break at set value analogue input
(Voltage at the analogue input < Limit value for cable break - see 2.39)
n_Low : Actual speed is less than limit speed for running monitor
(see 2.31 Limiting speed for running monitor)
Brake : Brake operation: set if exterior drive is applied in opposite direction with high
speed for prolonged period
UzLow : DC-link voltage low
TEI_high : Electronics interior temperature high
TM_high : Motor temperature high
TE_high : Output stage temperature high
P_Limit : Power limitation in mesh
I_Limit : Current limitation in mesh
3.11 DC-link voltage
Address : D013
Encoding:
][
256
][ VUzReference
bytes Data
VUz
Reference Uz ..........DC-link voltage reference variable (see 2.43 Reference value of DC-link voltage).