MODBUS LITE V5.01 parameter specification

Table Of Contents
MODBUS parameters "ebm-papst series 84 / 112 / 150 / 200"
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen, Germany ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo.: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 6 October 2003 ·File: ext001157859.doc ·Last printed 10/03/2015 15:13:00
·Page 9 of 70
Form 1003
1.3 Commands
1.3.1 Read holding register
Command code: 0x03
This command is used to read out the content of a number of holding registers.
Holding registers are parameters for which both read and write access are possible.
Command from master:
4 data bytes are transmitted:
1st MSB holding register address
1st LSB holding register address
Number of MSB addresses to be read
Number of LSB addresses to be read
The holding registers are described below.
Response from fan:
The following data bytes are transmitted:
Byte count (number of addresses to be read * 2)
Data in 1st MSB holding register
Data in 1st LSB holding register
Optional:
Data from the following holding registers (0 to n)
Exception codes:
In case of error, only one data byte (the exception code) will be transmitted
Exception codes:
0x02: Permissible range of the holding registers 0xD000 to 0xD3FF exceeded
0x03: Maximum telegram length for response (23 bytes) exceeded,
i.e. either more than 9 holding registers or 0 holding registers were requested.