PCA 2 1000D OPERATING INSTRUCTION25055055

HR
Mode
Function/Setting4. 5.
00 01 02 00 01 02
H18
x x
x x
DI2 function: 0 = OFF, 1 = 2D, 2 = 2D, 3 = 5D
H19
x x
x x
DI2 Signal: 0 = n.a. (no asignement), 1 = D1, 2 =
MODBUS, 3 = Timer
H20
x x
x x
DI3 function: 0 = OFF, 1 = 1D, 2 = 3D, 3 = 5D
H21
x x
x x
DI3 Signal: 0 = n.a. (no asignement), 1 = D1, 3 =
MODBUS, 3 = Timer
H22
x x
x x
DI-DI Relation: 0 = AND, 1 = OR
H23 x x x x x x
AO1 function: 0 = OFF, 1 = 2A, 2 = 17A
H24 x x x x x x
AO1 signal: 0 = n.a. (no asignement), 1 = A1
H26 x x x x x x
Limit message actual value: 0 = OFF, 1 = ON
H27 x x x x x x
Minimum actual value: 0 ...max. measuring range (Pa,
in.wg, m
3
/h, cfm)
H28 x x x x x x
Maximum actual value: 0 ...max. measuring range (Pa,
in.wg, m
3
/h, cfm)
H29 x x x x x x
Time delay limit message actual value: 0...120 (s)
H30
x
x
Limit message outdoor temperature: 0 = OFF, 1 = ON
H31
x
x
Minimum temperature:
-500 = OFF, -500...1500
-50.0...150.0 °C
(-580 = OFF, -580...3020
-58.0...302.0 °F)
H32
x
x
Maximum temperature:
1500 = OFF, -500...1500
-50.0...150.0 °C
(-580 = OFF, -580...3020
-58.0...302.0 °F)
H33
x
x
Time delay limit message actual value: 0...120 (s)
H34 x x x x x x
Limit message output voltage: 0 = OFF, 1 = ON
H35 x x x x x x
Minimal output voltage: 0 = OFF, 0...100
0...10 V
H36 x x x x x x
Maximum output voltage: 100 = OFF, 0...100
0...10 V
H37 x x x x x x
Time delay limit message output voltage: 0...120 (s)
H39
x x x
Nozzle coefcient (K-Factor): 1...max. value
H40 x x
x x
Control range: 0...max. measuring range (Pa, in.wg, m
3
/h,
cfm)
H41
x
x
Temperature range setpoint lowering:
0...1000
0.0...100.0 °C (0...1800
0.0...180.0 °F)
Operating Instructions PCA-2 1000D2 Programming
L-BAL-E295-GB 1906 Index 001 Part.-No.
42/48