6 Name plate and type key
Germany
Max. temperature of transported air:
380-415V~ YY / Y
50 Hz
1,48 / 0,22 kW
0,72 / 0,36
4,08 / 1,41 A
1458 / 736 r.p.m.
H
IP55
Date: 20210625
Item no.:
Number of certification:
2797-CPR-719672
Serial.no:
55°C - 300°C/2h
EN 12101-3 (2015)
IV 50-4/8 (B)
79013
1005405682-1
Systemair GmbH - Seefer Straße 45 - 97944 Boxberg - Germany
This powered smoke and heat control ventilator shall be installed as per the manufacturer´s instruction.
Installation and Operating Instructions are within the delivery.
Type:
2797
18
Made In:
gk28:thgieW
powered smoke and heat control ventilator
Voltage:
Frequency:
Nominal power at shaft (P2):
Nominal current:
Fan impeller speed:
Cos φ
:
Insulation class:
Protection class, motor:
Motor AOM Rated
18
0086
1
2
3
4
5
6
1
General data
2
Technical data
3
Temp./Time information/
only listed on smoke
extraction fans
4
Certifications and QR—
Codes
5
Manufacturer Address
Table 4 Type key
IV 100
-4/6 (-)(K), (B), (F)
Temperature- Time information (smoke extraction fan), see
Table 2 Temperature types, page 4
Number of poles
Thrust [N]
For exact data, see online catalogue.
IV
Induction fan
IV...EC
Induction fan
equipped with an EC motor
7 Installation
Safety information
Observe 2 Important safety information, page 1
Check the surface before installation for load bearing capacity.
Consider all static and dynamic loads when selecting hoisting equipment and fastening components.
Provide contact and intake protection and ensure safety distances according to DIN EN ISO13857 and DIN 24167-1.
Use installation material with fire resistance classes that meet temperature requirements.