UserManual S SA2 S SA2L202010

S-SA2
16/40 | User Manual S-SA2 & S-SA2L | 201905
Connecting S-SA2 to “multi” Ductwork Made of Boards
The S-SA2 smoke damper can be connected to “multi” ductwork made of calcium silicate boards tested according
to EN 1366-8. If mounted on a duct classied with lower re resistivity, the re resistivity of the S-SA2 smoke damper
will be decreased to the duct level.
This section does not depict duct hanger rules as those are dependent on the weight of the duct itself and must be
statically approved.
IMPORTANT: The interior of the S-SA2 smoke damper must remain accessible for maintenance.
Depending on the installation conguration, it may be necessary to create additional inspection panels
in the connecting ducts.
Legend for Figures of Connections to “Multi” Classied Ducts
1 Smoke damper S-SA2 (actuator side)
2 Accessory LEAS/Connected ductwork classied according EN 1366-9
3 Screw 5,5 DIN 7981 xing the damper through bendable hangers
4
When the damper is installed using
wet method: When the damper is installed using soft crossing method:
Gypsum plaster; mortar; concrete lling minimal category
M2.5, EN 998-2
Mineral wool lling 150 kg/m
3
and re resistive coating
CFS-CT (HILTI)
5 Cover plates thickness 10 mm placed on the opening circumference made of Promatect H (Promat)
6 Ductwork made of Promatect-L500 boards (Promat). Thickness of boards (P
t
) depends on the desired re resistivity.
7 Fire resistive coating Promat K84 (Promat)
Damper‘s horizontal blade axis orientation
Damper‘s vertical blade axis orientation
Connection Possibilities:
Multi-Single
Single-Multi
Multi-Multi