ITR DATA AND WIRING

DS-ITR-EN-000-SYS - 17 / 05 / 19
S.3.1.B.1
Key features
• Wide power supply range (110—240 VAC / 50—60 Hz)
• Automatic supply voltage detection
• Adjustable stepless output voltage
• Minimum speed adjustable by internal trimmer
• Kick start or soft start
Illuminated on/o switch
Technical specications
Power supply, Us 110—240 VAC / 50—60 Hz
Regulated output Umin—Us
Maximum load depends on the version
Unregulated output Imax. 2 A
Minimum output
voltage, MIN
30—60 of % Us
Maximum output
voltage, MAX
100 % Us
Kick start duration 8—10 s
Protection standard IP54 (according to EN 60529)
Ambient conditions
Temperature -20—35 °C
Rel. humidity 5—95 % rH (non-condensing)
Operational diagrams
Uout [%]
MAX MIN
Maximum
speed (Us)
Minimum
speed
Potentiometer position
Control curve
0
Uout [%]
t, [s]
Maximum
speed (Us)
Minimum
speed
Kick start duration time
Potentiometer position
Kick start mode
0
Uout [%]
t, [s]
Maximum
speed (Us)
Minimum
speed
Soft start duration time
Potentiometer position
Soft start mode
Article codes
Rated max. current [A] Fuse [A]
ITR-9-15-DT 1,5 (5*20 mm) F 3,15 A H 250 VAC
ITR-9-30-DT 3,0 (5*20 mm) F 5,0 A H 250 VAC
ITR-9-50-DT 5,0 (5*20 mm) F 8,0 A H 250 VAC
ITR-9-60-DT 6,0 (6,3*32) F 10,0 A H 250 VAC
ITR-9100-DT 10,0 (6,3*32) F 16,0 A H 250 VAC
Area of use
• Fan speed control of voltage controllable motors in ventilation systems
• For indoor use only
Standards
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC: EN 61000-6-3:2007/A1:2011/AC:2012
WEEE Directive 2012/19/EU
RoHs Directive 2011/65/EU
The ITR-9 series of electronic fan speed controllers regulate the speed of single-phase
(110—240 VAC / 50—60 Hz) voltage controllable motors by varying the supplied
voltage. The ITR-9 controllers provide automatic power supply detection. The minimum
speed is adjusted via an internal trimmer. The output is regulated by a potentiometer
in the range between the minimum output voltage and the supply voltage. The series
features an unregulated output for connecting a valve, lamp, damper, etc. There are two
start-up modes - kick start and soft start, selectable via a jumper.
www.systemair.com
ITR
Electronic fan speed controller

Summary of content (3 pages)