Air Distribution Products TFF Supply Valve Data Sheet
/ 12 | Valves Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ordering Code . . . . . . . . . . . . . . . . . . . . . . . . . 5 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . .
Valves | 3 / 12 Description TFF is a circular supply diffuser for ceiling installation. It has adjustable vent capacity and a 360° discharge pattern from which up to 180° can be shielded by a deflector. Highlights • Easy, precise air flow volume adjustment • Non-disturbant aesthetic form • Easy installation Accessories Detailed information about accessories for TFF is available on page • RFU and RFP: Mounting Frames Fig. 1: Air flow visualisation 6.
/ 12 | Valves Design TFF is made from galvanized steel sheet with powder colour coating. The product consists of the fixed part with fixing springs, equipped duct connection, the valve seat and the movable valve front plate. The front plate is held by the central thread bolt and can be moved by rotating. So the gap between the plate and the seat can be adjusted to set the required air flow volume.
Valves Ordering Code TFF- - 80 100 125 150 160 Size Colour øDN (mm) 200 Signal white RAL9003 White RAL9010 White RAL9016 Other RAL colour RALXXXX NOTE: The standard RAL colours have gloss 30%. Example of the Ordering Code TFF-125-RAL9003 Supply valve with nominal size 125 mm, with signal white coating RAL 9003.
/ 12 | Valves Accessories RFU & RFP Mounting Frames Tab. 2: Dimensions of RFU and RFP øA øD Installation opening diameter 80 100 71 78 100 120 97 103 øDN (mm) RFU RFP 125 146 122 128 150 170 147 153 160 180 157 163 200 220 197 203 Ordering Codes Description RFU, RFP are mounting frames for the valve TFF. They enable connection of the duct types that cannot be connected directly to the valve, like e.g. flexible ducts.
Valves Quick Selection Air flow volume at different sound power levels LwA 25 dB 30 dB 35 dB Type m³/h l/s m³/h l/s m³/h l/s TFF-80 38 11 45 13 52 14 TFF-100 55 15 69 19 81 23 TFF-125 121 34 142 39 160 44 TFF-150 126 35 151 42 172 48 TFF-160 145 40 172 48 196 54 TFF-200 205 57 251 70 289 80 NOTE: The working points were measured with 20 mm vent gap adjustment.
/ 12 | Valves TFF-100 TFF-80 10 Pa 70 12 14 16 18 5 mm 15 mm 10 mm l/s 15 Pa 70 20 25 45 dB(A) 20 mm 5 mm 60 60 15 mm 40 dB(A) 50 40 dB(A) l/s 20 mm 45 dB(A) 50 30 10 mm 40 35 dB(A) 40 35 dB(A) 30 30 30 dB(A) 20 20 30 25 dB(A) 40 50 60 TFF-80 25 dB(A) 50 70 m³/h Diagram 1: Pressure drop & A-weighted total radiated sound power level depending on air flow volume m 3 30 dB(A) 60 70 80 90 100 110 120 m³/h Diagram 3: Pressure drop & A-weighted total radiated so
| 9 / 12 Valves TFF-150 TFF-125 30 Pa 100 40 50 45 dB(A) 75 5 mm l/s 10 mm Pa 100 30 40 60 45 dB(A) 5 mm l/s 10 mm 15 mm 75 40 dB(A) 50 40 dB(A) 15 mm 20 mm 35 dB(A) 50 30 dB(A) 25 100 25 25 dB(A) 120 140 160 180 100 200 m³/h Diagram 5: Pressure drop & A-weighted total radiated sound power level depending on air flow volume m 30 dB(A) 20 mm 25 dB(A) 80 35 dB(A) 50 TFF-125 120 140 160 180 200 220 240 m³/h Diagram 7: Pressure drop & A-weighted total radiated so
/ 12 | Valves TFF-200 TFF-160 30 Pa 120 40 50 60 l/s 5 mm 40 Pa 50 60 70 45 dB(A) 150 45 dB(A) 80 90 5 mm 100 110 l/s 10 mm 100 10 mm 80 40 dB(A) 40 dB(A) 100 15 mm 15 mm 60 35 dB(A) 35 dB(A) 20 mm 30 dB(A) 40 50 30 dB(A) 20 mm 25 dB(A) 25 dB(A) 20 100 120 140 160 180 200 220 240 m³/h Diagram 9: Pressure drop & A-weighted total radiated sound power level depending on air flow volume m 5 TFF-160 120 160 200 240 280 320 360 400 m³/h Diagram 11: Pressure
Valves | 11 / 12 Installation, Maintenance & Operation Information about installation, maintenance and operation is available in the the instructions on Systemair DESIGN. “UserManual_TFF” document or follow Dry indoor conditions with an operation temperature range of -20°C to +70°C. Transport & Storage Dry indoor conditions with a temperature range of -40°C to +50°C. Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer.
www.systemair.com Systemair Production a.s.