Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   28 (56)  2018-07-11 
Fan compensation curve 1, 2, 3 
Speed 
 All speeds 
  Only low speed 
  Only normal speed 
  Only high speed 
  Low and normal speed 
  Normal and high speed 
Select the fan steps were the compensation shall be active 
Mode 
 Off 
  In all modes 
 Only when defrosting 
Fan 
  Supply air fan and extract air fan 
  Supply air fan only 
  Extract air fan only 
Sensor 
 “Temperature sensor” 
 “Pressure sensor” 
 CO2 sensor 
 RH sensor 
All active temperature sensors and differential pressure sensors will be included in 
the "scroll list" for selectable sensors 
Operation settings:  Data & Settings > Fan control > Fan compensation 
Settings to set up the compensation curve 
Fan compensation curve 1, 2, 3 
Low point 
  Input value  break point for selected sensor 
 Compensation  compensation value (negative or positive adjustment) 
Middle point 
  Input value  break point for selected sensor 
 Compensation  compensation value (negative or positive adjustment) 
High point 
  Input value  break point for selected sensor 
 Compensation  compensation value (negative or positive adjustment) 
  Support control 
Activate  Configuration > Function Configuration > Function Activation 
Support control 
 No 
 Yes 
Configure  Configuration > Function Configuration > Support control 
Enable support control when ventilation unit is shut down 
 No 
 Yes 










