Extract air fan setpoint type when smoke alarm 
 Off/Auto normal setpoint 
 Manual setpoint 
 Manual outputs 
  Low speed setpoint 
  Normal speed setpoit 
  High speed setpoint 
Manual setpoint or output (Extract air fan) 
 0..100% 
 0.. 
Outdoor air damper function when fire alarm 
  Normal function (follow the fan) 
 Always open 
 Always closed 
Exhaust air damper function when fire alarm 
  Normal function (follow the fan) 
 Always open 
 Always closed 
Operation settings:  Data & Settings > Fire/Smoke 
  Humidity/Dehumidity 
Activate:  Configuration > Function Configuration > Function Activation 
 No 
 Humidity 
 Dehumidity 
 Humidity+Dehumidity 
Configure:  Configuration > Function Configuration > humidity/Dehumidity 
Operation settings:  Data & Settings > Humidity controller 
General 
Humidity control can be configured as Humidification, Dehumidification or both 
Humidification and Dehumidification. 
Two humidity sensors can be connected, a room sensor for control and an optional 
duct sensor for maximum limiting. The limit sensor can be omitted. 
The humidity control is handled by a PI-controller. 
The humidity sensors must give 0…10 V DC for 0…100 % RH. 
Humidification 
An analogue output is used to control a humidifier. The output will increase on 
decreasing humidity. A digital output can also be used to start a humidifier. 
Maximum limitation function using duct humidity sensor: 
If the maximum limitation is 80 % RH and the hysteresis is 20 % RH, the controller 
output signal will begin decreasing at 60 % RH. When halfway to 80 % RH (i.e. when 
at 70 % RH), half the output signal will be damped. If the humidity in the duct still 
reaches 80 % RH, the entire output signal will be damped. 