Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   37 (56)  2018-07-11 
Dehumidification 
An analogue output is used to control a dehumidifier. The output will increase on 
increasing humidity. A digital output can also be used to start a dehumidifier. 
Humidification/dehumidification 
An analogue output is used to control a humidifier. The output will increase on 
decreasing humidity. 
The cooling output Y3 will be activated for dehumidification through condensation. The 
output will increase on increasing humidity. This signal overrides the cooling signal 
from the temperature controller so the output can be activated for dehumidification 
even if the temperature controller demand is zero. 
For good temperature control when using cooling for dehumidification it is important 
that the cooler is placed first in the air stream so that the exchanger and heater can be 
used to reheat the air after dehumidification. 
Digital humidity signal 
A digital output signal, "Dehumidification/Humidification", can be used for on/off control 
of humidifiers/dehumidifiers. The output signal has an Activate value and a Deactivate 
value which are connected to the humidity controller output. The signal is activated 
when the humidity controller output rises above the set Activate value and is 
deactivated when the humidity controller output drops below the set Deactivate value. 
If a start signal is needed for a cooling unit or a magnetic valve for DX 
dehumidification, the digital output signal “Start P1-Cooling” should be used. In this 
case, the “pump” stop delay should be set to 0 s. 
  Filter monitor 
Activate:  Configuration > Function Configuration > Function Activation 
 No 
 Yes 
Configure:  Configuration > Function Configuration > Filter monitor 
Type 
  DI  Digital pressure guard 
 AI  Analog pressure transmitter 
Placement 
 Supply 
 Extract 
  Supply & Extract 
Filter alarm reset 
 No 
  Yes  Reset the calender counter. 
Fiter alarm time (month) 
  Time to next filter replacement 
Analogue filter monitoring may be made air flow dependent. This means that a 
higher pressure drop is permitted across a filter at a higher air flow. For this 
purpose, X and Y coordinates are used to set the linear function that should be 