Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   41 (56)  2018-07-11 
  Extra time channel 4 
Stop delay motor control 1 
 0.. s 
Motor control 2 
 None 
 Motor protection 
 Run indication 
Mode motor control 2 
  Only Digital input 
  Normal time channel 
  Extra time channel 4 
Stop delay motor control 2 
 0.. s 
Operation settings:  Data & Settings > Fan control > Extra fan motor control 
  Damper 
Activate:  Configuration > Function Configuration > Function Activation 
 None 
 Outdoor 
 Outdoor+Exhaust 
 Exhaust 
Outdoor damper follow supply air fan and exhaust damper follow extract air fan 
Outdoor air damper stop delay 
Operation settings:  Data & Settings > Fan control > Supply air fan 
 0 s 
Exhaust air damper stop delay 
Operation settings:  Data & Settings > Fan control > Exhaust air fan 
 0 s 
  Extra Indication & outputs 
Activate:  Configuration > Function Configuration > Extra Indication & outputs 
Extra time channel 
 None 
 1 
 2 
 3 
 4 
Note!  Time channel 4 are used also for recirculation 
Running indication 
 No 
 Yes 