Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   42 (56)  2018-07-11 
Alarm outputs 
 None 
  A/B-alarm     1 pcs Digital output 
  A-alarm + B-alarm    2 pcs digital outputs 
  A-alarm + B/C-alarm  2 pcs digital outputs 
Alarm priorities 
Alarms can be given different priority levels, A-alarm, B-alarm, C-alarm or not 
active. Digital outputs can be bound to act as alarm outputs for A/B-alarms on one 
digital output or both A- and B alarms (or B/C-alarm) on different digital ouptuts. 
The digital outputs can be inverted, so that an inoperative alarm gives a high 
output and vice versa. A- and B-alarms must be acknowledged to reset. C-alarms 
automatically reset as soon as there is no longer a cause for alarm. 
Digital outputs 
Selection A/B-alarm 
A-alarm and B-alarm indicates on digital output Alarm 1 
Selection A-alarm + B-alarm 
A-alarm indicates on digital output Alarm 1 
B-alarm indicates on digital output Alarm 2 
Selection A-alarm + B/C-alarm 
The A-alarm indicate on digital output Alarm 1 
B-alarm and C-alarm indicate on digital output Alarm 2 
Free cooling running 
 No 
 Yes 
To use digital output too indicate when free cooling running. 
  Extra sensors & inputs 
Activate:  Configuration > Function Configuration > Extra sensors & inputs 
Alarm achnowledgement 
 No 
 Yes 
Activate Digital input for remote control of acknowledgment 
Extra temperature sensor 
 None 
 1 
 2 
 3 
 4 
 5 
The input signals ”Extra Sensor 1”, ”Extra Sensor 2”, ”...”, ”Extra Sensor 5”, can be 
used to add extra temperature sensors for supervision of temperatures that are not 