   7 (56)  2018-07-11 
  Extract air cascade] 
  Outdoor dependent supply air or room 
  Outdoor dependent supply air or extract air 
  Outdoor compensated room cascade 
  Outdoor compensated extract air cascade 
  Extract air depending supply air 
The supply air temperature is kept at the setpoint value by controlling the output 
signals for "Heating (Sequence-A)", "Exchanger (Sequence-B)", "Cooling 
(Sequence-C)", "Heating 2 (Sequence-G)” and “Cooling 2 (Sequence-H). Up to 10 
sequences (Sequence-A..J) with separate PID control settings for each sequence 
can be used. 
A neutral zone can be set around the setpoint value. 
Example: 
If the setpoint is 18 °C and the neutral zone is 2 K, the cooling setpoint will be 19 
°C and the heating setpoint will be 17 °C. If the supply air temperature is in the 
neutral zone, the heating and cooling will be blocked. If the supply air temperature 
decreases below the setpoint –NZ/2 the heating signal will be active until setpoint 
is fulfilled. If the supply air temperature increases above the setpoint +NZ/2 the 
cooling signal will be active until setpoint is fulfilled. 
The setpoint value is set using the NaviPad or alternatively using an external 
setpoint device. Alarms which are activated when the supply air temperature is too 
high or too low are active. Alarm for control offset of the supply air temperature is 
active. 
Supply air 
The supply air temperature is kept at the setpoint value by controlling the output 
signals. The controller is reverse acting, i e. the output will increase for decreasing 
temperature. 
Outdoor compensated supply air 
The supply air temperature setpoint is outdoor temperature compensated using a 
control curve with 4 node points. 
Room cascade 
Cascade control of room temperature and supply air temperature to achieve a 
constant, settable room temperature. The room controller output signal generates 
the supply air controller’s setpoint value. The room controller used an own PI 
loops. 
1..4 room sensors can be connected. If 2..4 sensors are connected, the average of 
their values will be used. 
Extract air cascade 
Cascade control of extract air temperature and supply air temperature to achieve a 
constant, settable room temperature. The extract air controller output signal 
generates the supply air controller’s setpoint value. The extract controller used an 
own PI loop. 
Outdoor dependent supply air or room 
Outdoor temperature dependent switching between supply air temperature control 
and room temperature control. 