QUICK CONFIGURATION GUIDE ACCESS SW 4 0 1 04 TO 4 6 1 00 157618A008
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 How to use the configuration wizard
- 4 Save commissioning settings
- 5 Quick configuration guides
- 5.1 Editable naming
- 5.2 Alarm configuration
- 5.3 Fan control type (Pressure)
- 5.4 Temperature control type (Room)
- 5.5 Extended operation
- 5.6 Fan compensation
- 5.7 Air quality control (Fan start/stop)
- 5.8 Fire/Smoke function (Fire)
- 5.9 Free cooling
- 5.10 External cooler (DX)
- 5.11 External heater (Water)
- 5.12 Changeover
- 5.13 External stop
- 5.14 Support control
8
| Quick configuration guides
5.3.3 Operation settings
Adjust the fan pressure set points in the Data & Settings > Fan Control > Fan setpoints menu.
Overview:
Data & Settings > Fan control > Fan setpoints
24 Jun 10:31
Setpoint low speed supply air fan 100 Pa
Setpoint low speed extract air fan
100 Pa
Setpoint normal speed supply air fan 200 Pa
Setpoint normal speed extract air fan
200 Pa
Setpoint high speed supply air fan 200 Pa
Setpoint high speed extract air fan
200 Pa
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Fan control
3. Select Fan setpoints
4. Select and adjust setpoints for the available fan speed levels.
5.4 Temperature control type (Room)
5.4.1 Activation
Activate room temperature control.
Select Cascade room temp control as temperature control type in the Configuration > Functions > Func-
tion activation menu.
Overview:
Configuration > Functions > Function activation
24 Jun 10:31
Temperature control type
Room cascade
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Room cascade as Temperature control type.
157618 | A008