ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 Save commissioning settings
- 4 Quick configuration guides
- 4.1 Editable naming
- 4.2 Alarm configuration
- 4.3 Fan control type (Pressure)
- 4.4 Temperature control type (Room)
- 4.5 Extended operation
- 4.6 Fan compensation
- 4.7 CO2 control (Fan start/stop)
- 4.8 Fire/Smoke function (Fire)
- 4.9 Free cooling
- 4.10 External cooler (DX)
- 4.11 External heater (Water)
- 4.12 Change over
- 4.13 External stop
- 4.14 Support control
Quick configuration guides |
5
2. Select Alarms
3. Select the desired alarm after scrolling through the list of all alarms and identifying the alarm via either name or alarm
number
4. Select the action the unit will take when the alarm is active (e.g Normal stop) as Action
5. Select the desired Alarm class or disable the alarm (e.g Class B) as Level
6. Adjust the time before the alarm activates as Delay
7. Adjust the name of the alarm as Name.
4.3 Fan control type (Pressure)
4.3.1 Activation
Activate pressure control.
Select Fan control type as Pressure in the Configuration > Functions > Function activation menu.
Overview:
Configuration > Functions > Function activation
04 Apr 13:54
Fan control type
Pressure
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Pressure as Fan control type.
4.3.2 Allocation
Setup differential pressure sensors.
Select I/O (in-/output) placement for where the differential pressure sensors are connected. Set the sensors’ signal and
corresponding measuring range in the Configuration > I/O allocation settings > Analog inputs menu.
Caution
Do not use the same in- or output for several functions.
Overview:
Configuration > I/O allocation settings > Analog
inputs
04 Apr 13:54
Analog inputs
Device Position
Pressure supply air
Controller
UI2
Pressure extract air Controller
UI1
157618 | A002