Configuration Manual
Version Document 
A
001 
A
ccess V4.X Configuration manual 
   24 (56)  2018-07-11 
3.4 Damper 
Activate:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type 
Activate Recirculation (Recirculation 2) 
Example:  Order heating sequence: 
1. ”Exchanger” 
2. ”Heating” 
3. ”Recirculation” 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 2 0% 0% Cooling 
Sequence-D  3 Off  Off 0% 0% Recirculation 1 
Sequence-E Off Off 0% 0% Recirculation 2 
Sequence-F Off Off 0% 0% Fan heating/cooling 
Sequence-G Off Off 0% 0% Heating 2 
Sequence-H Off Off 0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
Activate Recirculation and Recirculation 2 
Example:  Order heating sequence: 
1. ”Exchanger” 
2. ”Heating” 
3. ”Recirculation 2” 
4. “Recirculation” 
Sequence  Heating  Cooling  Start 
Heating 
Start 
Cooling 
Sequence name 
Sequence-A 2 Off 0% 0% Heating 
Sequence-B 1 1 0% 0% Exchanger 
Sequence-C Off 2 0% 0% Cooling 
Sequence-D  4 Off  Off 0% 0% Recirculation 1 
Sequence-E  3 Off  Off 0% 0% Recirculation 2 
Sequence-F Off Off 0% 0% Fan heating/cooling 
Sequence-G Off Off 0% 0% Heating 2 
Sequence-H Off Off 0% 0% Cooling 2 
Sequence-I Off Off 0% 0% Exchanger extract 
Sequence-J  Off  Off  0%  0%  Extra heating/cooling capacity 
Configure:  Configuration > Function Configuration > Function Activation> Sequence Configure 
type > Recirculation (Recirculation 2) 
Operation settings:  Data & Settings > Temperature control > Recirculation (Recirculation 2) 