4.6 Fan compensation
4.6.1 Activation
Select Yes for Fan Compensation in the Configuration > Functions > Function activation menu.
Overview:
Configuration > Functions > Function activation
04 Apr 13:54
Fan compensation curves
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Set Yes on Fan compensation curves
4.6.2 Configuration
Select and configure a fan compensation curve in the Configuration > Functions > Fan compensation curves
menu.
Overview:
Configuration > Functions > Fan compensation curves
04 Apr 13:54
Fan compensation curve 1
>
Fan compensation curve 2
>
Fan compensation curve 3
>
Configuration > ... > Fan compensation curve 1
04 Apr 13:54
Fan level All levels
Mode Inactive
Fan
Supply air fan + Exhaust air fan
Sensor Select I/O
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Fan compensation curve 1/2/3
4. Select which fan level(s) the compensation curve should apply to as Fan level
5. Select when the compensation curve is active as Mode
6. Select which fan the compensation curve applies to as Fan
7. Select which of the available sensors to use for compensation.
157618 | A002