ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 Save commissioning settings
- 4 Quick configuration guides
- 4.1 Editable naming
- 4.2 Alarm configuration
- 4.3 Fan control type (Pressure)
- 4.4 Temperature control type (Room)
- 4.5 Extended operation
- 4.6 Fan compensation
- 4.7 CO2 control (Fan start/stop)
- 4.8 Fire/Smoke function (Fire)
- 4.9 Free cooling
- 4.10 External cooler (DX)
- 4.11 External heater (Water)
- 4.12 Change over
- 4.13 External stop
- 4.14 Support control
Quick configuration guides |
17
4.8.3 Allocation
Select I/O (in-/output) placement of where fire alarm activation input, fire damper output and position feedback input
are connected to the controller in the Configuration > I/O allocation settings submenus Digital inputs
and Digital outputs.
Overview:
Configuration > I/O allocation settings > Digital
inputs
04 Apr 13:54
Digital inputs
Device Position
Fire alarm Controller DI5
Feedback fire damper
Controller
DI6
Configuration > I/O allocation settings > Digital
outputs
04 Apr 13:54
Digital outputs
Device Position
Fire damper
Controller DO5
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the fire alarm contact/sensor (e.g. DI5) as position for Fire alarm
Note:
Step 5-8: Only applicable if fire dampers are configured.
5. Select the input connected to the fire damper position switches (e.g. DI6) as position for Feedback fire damper
6. Go back to I/O allocation settings (use the navigation path Configuration > I/O allocation
settings)
7. Select Digital outputs
8. Select the output connected to the fire damper (e.g. DO5) as position for Fire damper.
157618 | A002