ACCESS QUICK CONFIG GUIDE SW 4 0 1 05 157618
Table Of Contents
- 1 About this document
- 2 How to set up a function
- 3 Save commissioning settings
- 4 Quick configuration guides
- 4.1 Editable naming
- 4.2 Alarm configuration
- 4.3 Fan control type (Pressure)
- 4.4 Temperature control type (Room)
- 4.5 Extended operation
- 4.6 Fan compensation
- 4.7 CO2 control (Fan start/stop)
- 4.8 Fire/Smoke function (Fire)
- 4.9 Free cooling
- 4.10 External cooler (DX)
- 4.11 External heater (Water)
- 4.12 Change over
- 4.13 External stop
- 4.14 Support control
Quick configuration guides |
23
4.10.4 Operation settings
Adjust the start/stop point for the digital output: Cooling start (SEQ-C) in the Data & Settings > Temperature
control > Cooling menu.
Overview:
Data & Settings > Temperature control > Cooling
04 Apr 13:54
Digital start output start point 10 %
Digital start output stop point 1 %
Data & Settings > Temperature control > Supply air
controller
04 Apr 13:54
Min limit supply air
14 °C
Max limit supply air
30 °C
Reduction of min limit supply air if active DX-cooling
5 °C
Step by step:
1.
Select Data & Settings from the navigation icons
2. Select Temperature control
3. Select Cooling
4. Set the desired output % to activate the digital output as Digital start output start point
5. Set the desired output % to deactivate the digital output as Digital start output stop point
6. Go back to Temperature control (use the navigation path Data & Settings > Temperature control)
7. Select Supply air controller
8. Adjust the min. allowed supply air temperature when DX-Cooling is active as Reduction of min limit supply
air if active DX-cooling.
157618 | A002