Quick configuration guides |
31
5.13.2 Allocation
Select the I/O (in-output) placement of where the external stop switch is connected to the controller in the Configu-
ration > I/O allocation settings > Digital inputs menu.
Overview:
Configuration > I/O allocation settings > Digital
inputs
24 Jun 10:31
Digital inputs
Device Position
External stop
Controller
DI6
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Digital inputs
4. Select the input connected to the external stop switch (e.g. DI6) as position for External stop.
5.14 Support control
5.14.1 Activation
Set Support control to Yes in the from the list of available function in the Configuration > Functions > Func-
tion activation menu.
Overview:
Configuration > Functions > Function activation
24 Jun 10:31
Support control
Yes
Step by step:
1.
Select Configuration from the navigation icons
2. Select Functions
3. Select Function activation
4. Select Yes as Support control