Commissioning Record
Table Of Contents
4
|
Function settings
Function
Default setting Set value
Summer/Winter mode
⊠ No
□ Yes
No
Yes
Summer mode temperature set point □ Supply __________°C Supply °
□ Extract
__________°C
Extract
°
□ Room __________°C Room
°
Switch between cascade control during
Summer and outdoor compensated
supply control during Winter
□ No
□ Yes
No
Yes
Type of switch to indicate Summer □ Calender Calender
From Date:
_____
Month:
_____
From Date:
Month:
To Date:
_____
Month:
_____
To Date:
Month:
□ Digital input
□ Outdoor temp.
> 13 °C
Digital input
Outdoor temp.
>
If outdoor comp. temp. control
Outdoor temp/setpoint
Curve point 1, 2, 3, 4:
-20 / 25 °C °
-10 / 23 °C
°
0 / 22 °C
°
10 / 18 °C
°
If cascade control:
Min supply air temp. limit 14 °C °
Max supply air temp. limit
30 °C
°
Cooling recovery
Mode
⊠ On
□ Off
On
Off
Start at temp. difference
2 °C
°
Cooling
Type of cooler
□ Water
□ DX
Water
DX
If water cooler
Type of feedback, pump
□ None
⊠ Alarm
□ Run indication
None
Alarm
Run indication
Pump stop delay
5 min
min
162527 | A004